Menu
← Back to AC & DC Load Bank
EDPN 110LB300-K Battery Capacity Tester

AC & DC Load Bank

EDPN 110LB300-K Battery Capacity Tester

125 Vdc (90 – 150 Vdc), 0 – 300 A Constant Current DC Load Bank

  • 90 – 150 Vdc / 0 – 300 A
  • LCD real-time V / A / Ah
  • 3 adjustable stop points

Datasheet

CategoryDC Load Bank

Enquire

Summary

The only way to know your stationary batteries will perform according to the specification is to test the batteries’ capacity with a DC load bank.

IEEE recommends load testing for Vented Lead-Acid and Ni-Cad stationary batteries every 5 years and VRLA stationary batteries every 12 months.

The EDPN constant current DC load testers are an easy and affordable way to perform accurate IEEE 450 (Vented Lead-Acid), IEEE 1106 (Ni-Cad) and IEEE 1188 (VRLA) load tests.

These units are quick and easy to set up. They display the voltage, current and Ah removed during the test. Furthermore this is a constant current load bank, the user does not have to do manually adjust the current during the tests.

The load banks are standardized with multiple auto-stop settings and built-in protection to ensure that the batteries are never damaged due to over discharge.

Features

  • Constant current load bank holds the current set throughout the test.
  • LED screen displays real time voltage, discharge current and Ah removed
  • Units can be paralleled with the 110LB120-T if data acquisition/ individual cell monitoring required
  • Easily adjust settings electronically
  • 3 adjustable stop points * End system voltage * Discharge time * Discharge capacity (Ah)

Includes

  • Hard carrying case
  • 3 meter DC cable
  • Instruction manual

Built-in protection

  • Audible alarm
  • Warning on LED screen
  • High temperature shutdown
  • High voltage shutdown
  • Over load protection

Specifications

Technical specifications

DISPLAYLCD displays real time voltage/ current/ test time/ Ah discharged
INPUTEnd system voltage/ test time/ Capacity discharged (Ah) – adjustable
TEST TYPEUnit controls the current so it stays where it is set throughout the test
PROTECTIONOver heat/ Over load/ Over voltage protection with audible alarm and screen warning
POWER SUPPLY220 Vac, 50 Hz (Option: 110 Vac, 50/60Hz)
DC CABLES120mm2, 3 meter (included)
DIMENSIONSL915mm x W230mm x H635mm + 10mm
WEIGHT50 kg (main unit only, not included hard case, DC cables)
Request QuotationTechnical Consultation
Contact Us