EDPN 220LB300-T Battery Capacity Tester
- 190 – 300 Vdc / 0 – 300 A
- 7" LCD, USB / RS-485
- 3 adjustable stop points
AC & DC Load Bank
10 – 240 Vdc, 0 – 120 A Constant Current DC Load Bank
Battery discharge testing is still the most accurate and reliable method for evaluating the actual capacity of a battery group, because only constant current discharge can perfectly simulate the working status of the batteries under load.
Because DC power systems in industrial utilities use different battery voltage levels (24 V, 48 V, 110 V, 120 V, 220 V, 240 V), the 110LB120-T is built as an unattended, automatic instrument with intelligent stop points and wide voltage variability for almost all battery types.
| 10 ÷ 15 V | 0 ÷ 60 A |
|---|---|
| 21.6 ÷ 58 V | 0 ÷ 120 A |
| 86 ÷ 140 V | 0 ÷ 120 A |
| 180 ÷ 240 V | 0 ÷ 60 A |
| Max. extension current | 720 A max. (120 A internal + 600 A external) |
| Internal current range | 0 ÷ 120 A |
|---|---|
| Accuracy & resolution | ≤ ±0.5 %, 0.1 A |
| External current range | 0 ÷ 600 A (optional current clamp) |
| Accuracy & resolution | ≤ ±1 %, 0.1 A |
| Group voltage range | 10 ÷ 300 V |
|---|---|
| Accuracy & resolution | ≤ ±0.5 %, 0.1 V |
| Cell voltage range | 0 ÷ 15 V |
| Accuracy & resolution | ≤ ±0.5 %, 0.01 V |
| Power supply voltage | 220 VAC (-20 % / +30 %) |
|---|---|
| Frequency | 50 / 60 Hz |
| Power consumption | 350 W (max) |
| Communication port | USB / RS232 |
|---|---|
| Internal memory | 8 Mbit Flash |
| LVD standards | 2006/95/EC : EN 61010-1:200 |
|---|---|
| EMC standards | 2004/108/EC Annex II: EN 61000-6-1:2007, EN 61000-6-3:2007, EN 61000-3-2:2006+A2:2009, EN 61000-3-3:2008 |
| Operating temperature | -5 ÷ 50 °C |
|---|---|
| Storage temperature | -40 ÷ +70 °C |
| Humidity | 5 % – 95 % RH |
| Altitude | below 1000 m |
| Working noise | < 60 dB (at 1 m) |
| Main tester | 230 x 370 x 670 mm |
|---|---|
| Carrying case | 370 x 600 x 800 mm |
| Weight | 24 kg (main tester) / 46 kg (gross) / 0.3 kg (each wireless module) |
| 110LB120-T | Battery discharger & capacity tester |
|---|---|
| LB-AS | PC analysis software |
| HEC-100A | 100 A current clamp |
| HEC-200A | 200 A current clamp |
| HEC-600A | 600 A current clamp |
| ED-24612 | Wireless module for 2 V / 4 V / 6 V / 12 V |
| ED-122 | Wireless module for 1.2 V / 2 V |