Menu
← Back to Industrial UPS

XP90i DC/AC UPS - ATEX IECEx

Chloride® XP DC/AC UPS Inverter systems are tailor-made solutions designed to operate in the hazardous atmosphere.

Enquire
UPS TypeDC/AC Inverter IECEx
Rating< 80 kVA
TechnologyIGBT
◎Contact Us

Market & Industry Type

  • Offshore production process in Explosion-risk areas
  • Wellhead platforms / Unmanned platforms
  • Pipelines instrumentation
  • Refineries

Downloads

⌄
Features & BenefitsRead less ⌃

Key features

Small footprintTo optimize space on offshore platform.
DurabilityOptimized thermal management.
ImmunityStrong immunity to perturbations.
Safe control, door closedAllows the user to operate the switches, circuit breakers, and control buttons door closed.
Smart access to UPS dataLarge graphical user interface on the front.
Safe and easy maintenanceOnce open, the front door gives direct access to all components.
AlarmsEmbedded event logger (up to 2000 events). Close range Wi-Fi module - To download the event logger without opening the equipment enclosure.
Technical SpecificationsRead less ⌃

Output

AC Voltage1 x 230V (220, 240) 1 x 110V (115, 120) 3 x 400 V (380, 415)
Frequency50 Hz (60 Hz)
Overload inverter: 1 minute150 % of nominal power
Overload inverter: 10 minutes125 % of nominal power
Short circuit clearance: 1-ph output (in % of nominal current)250 %/100 ms - 175 %/5 s
Short circuit clearance: 3-ph output (in % of nominal current)315 %/100 ms - 220 %/5 s (Ph-N)
Power factor0.8 lagging
Allowable crest factor3/1

Battery

TypeValve Regulated Lead Acid (VRLA) Recombinaison Nickel Cadmium
AutonomyFrom few minutes to several hours, as per customer’s requirement
Battery current limitation (typical, float, mode)0.1 (Lead Acid or Nickel Cadmium battery)
Battery temperature compensation-3 mV / °C / cell

General Data

Operating temperature
Relative humidity100% condensing
Operating altitude1000m max without derating
CoolingNatural

Enclosure

DesignATEX/IECex certified forZone1, II 2G Ex d IIB+H2 T3 (IEC 60079)
MaterialStainless steel (SS316L),Carbon steel (mild steel) or Aluminum
External ingress protectionIP 66 according to IEC 60529
DimensionsVarying according to ratings & options

Example of Chloride UPS

The objective of this video is to show a Chloride full solution implemented with explosion proof UPS + battery implemantation + battery monitoring system + software application.

Visit our channel ↗
Contact Us