Menu
← Back to Industrial UPS

Chloride® CP70i DC/AC Inverter

CP as Customized Product. The most advanced product in terms of possibilities.

Enquire
UPS TypeDC/AC IEC/NEC
Ratings5 to 320 kVA
TechnologyIGBT
◎Contact Us

Market & Industry Type

  • Power generation plants
  • Transmission and Distribution substations
  • Oil & Gas industries, offshore and onshore

Downloads

⌄
Features & BenefitsRead less ⌃

Key advantages

MaintainabilityThe easiest on the market with total components front access.
ReliabilityInnovative internal temperature reduction, through dual redundant cooling channels. Multiplied redundancy with Chloride® Patented Smart Parallel Switching function that dynamically controls paralleled systems.
User friendlyLarge color touch screen with 2000-event exportable log. One of the best on the Industrial UPS Market.
USB accessExport of all the recorded events using USB flash drive. Memorization of complete electronic settings for future maintenance needs.
Batteries compatibilityInnovative full integration with SMC/Salt Batteries (Sodium Metal Chloride Batteries). Full compatibility with Lead-acid, nickel-cadmium batteries, sealed or vented and Lithium-Ion.
Life timeDesigned for 20+ years of continuous operation with appropriate maintenance plan.
Technical SpecificationsRead less ⌃

Input

DC voltage110-120 V 220-240 V 400 V
Input voltage range88-156 V 176-305 V296-507 V

Output

AC Voltage Single phase1 x 230 V (220, 240) ; 1 x 110 V (115, 120)
AC Voltage Three phase3 x 400 V (380, 415) ; 3 x 220 V (200, 208, 230)
Frequency50 Hz (60 Hz)
Frequency stability with internal oscillator+/- 0.05%
Frequency stability with reserve synchronism+/- 3 % (from 1 to 5% adjustable)
Voltage stability (for 0 to 100 % load variation): Static+/-1 % (+/-2 % for parallel systems)
DynamicVFI SS 111 as per IEC/EN 62040-3, class 1
Inverter overload capability: 1 minute150 % of nominal power
Inverter overload capability: 10 minutes125 % of nominal power
Short-circuit clearance (in % of nominal current)1-ph output : 250 % / 100ms - 175% / 5s
3-ph output Ph-N315 % / 100 ms - 220 % / 5 s
3-ph output Ph-Ph190 % / 100 ms - 135 % / 5 s
Harmonic voltage distorsionWith 100 % linear load < 3 %
Harmonic voltage distorsionWith 100 % non-linear load : SS as per IEC/EN 62040-3
Allowable power factor0,5 lagging to 0,5 leading

General Data

Operating temperature0 to 40 °C (-20°...55°C on request)
Storage temperature-20 to +70°C
Relative humidity< 95% non condensing
Operating altitude1000m max without derating
CoolingForced ventilation
EfficiencyUp to 90% according to rating
External protectionIP 20 according to IEC 60529
Internal protectionProtection against unintentional direct contacts, as per IEC 60950-1
Noise (at 1m in front of the unit)60-75 dB according to rating
Cabinet colourGrey RAL 7032
DimensionsVarying according to ratings and options

Ratings

Output power (kVA)5 to 500
DC Input voltage (Vdc)110-220 220-240 400

Options

InverterAutomatic precharge of capacitors Onther output voltage (1 x 110 to 3 x 690 VAC) Inverter oversizing
By pass lineBypass isolator(s) Bypass transformer (H class) Bypass stabilizer (servo-controlled) Backfeed protection
SystemInverter with or with bypass line Parallel configurations Input / output isolators AC Distribution Earth fault detection or monitoring Internal lighting Anti-condensation heater Cabinet temperature monitor
MechanicalExternal ingress protection up to IP42 Top cable entry Specified color of panels Special feet height (200mm or 300mm) Special keylock Non-magnetic gland plate (brass or aluminum) Lifting eyes 2 mm side panels thickness Specified cabinet identification (tag, nameplate) Anti-seismic design
CommunicationFront panel analogue meters(72x72, class 1.5 or class 1) Transducers 4-20mA Additional volt-free contacts Modbus RTU (RS232 or RS485) Modbus / TCP Profibus IEC61850 protocol PPVis monitoring software Mimic panel on front:• Passive mimic of the system• Active mimic with integrated LEDs Lamp indicator on front panel (22 mm diameter)

Standards

StandardsIEC62040-1:2008+AMD1:2013 IEC62040-2:2006 IEC62040-3:2011 IEC61439-1:2011 IEC60529:1989+AMD1:1999 IEC60076-11:2004 Protecting the power that powers the world Global Headquarters and France UK Office (North Sea) UK Office Eastern Regional Office Spain Office Middle East & levant Regional North America Office Asia Pacific Office © 2026 Copyright Website by
Contact Us